Integral Starter Unit
D.1 This is a field based operating unit, with electronic control logic, mounted on the actuator itself, for the unit functions
like Open-Stop-Close and Local-Off-Remote with the help of lockable switch can be from this unit. This units can
operate between-20 C to 80 C
D.2 Three Position Switch / Push buttons are provided for Open-Stop-Close functions also Open-Close indications
lamps/LED are provided for full Open/Full Close position
D.3 Coupled with the actuator the entire assembly conforms to weather proof standard IP67
D.3 Status annunciations LED, which are available,
Actuator running in Open
Actuator running in Close
Actuator in Local operation
Actuator in Remote operation
Open limit switch tripping
Close limit switch tripping
Actuator in inching mode
Actuator in self-retaining mode
24VDC control colt availability for customer use
D.5 Electromechanically interlocked contactors of 230V, 1phase 50Hz AC are provided in the starter unit
D.6 The starter unit has the following field selectable options, on demand. Closing by torque or closing by travel Remote
operation can be dome by inching/non inching mode
D.7 Potential free contacts ate available for
Thermal Over Load Relay trip
Torque switch trip
Thermo switch trip
Local-Off-Remote positions
Annunciation of power failure
D.8 Time delay is introduced between tripping of torque switch in closing direction and torque switch in open direction
D.9 Potential free contacts are available for power failure annunciation
D.10 Automatic phase sequence corrector facility is available,
D.11 24VCD remote command signal (Open-Stop-Close) from DCS shall be opto-isolated from electronics
D.12 The following modes available through DIP switches & are field congifigurable:Inching or non-inching, Valve seating
by close torque or close limit
D-13 Fault annunciation LED are available
Torque Switch Open
Torque Switch Close
Thermo switch trip
Thermal Over load Relay trip
Motor Single phasing
D.14 It will be possible to reverse the direction of travel (in local & remote) without giving stop command is self retaining
as well as non-self retaining mode.
The unit will have interchangeable PCB which will be split into different functional modules mounted on mother board for
easy interchangeablity, The basic actuator and starter unit will be with Plug in type connectors.
E Positioner
E.1 Positioner will accept 4-20A control signals and give an outpur of 230 VAC, 10A Up/ Down relay signals.
E.2 This unit will have an adjustable dead band from 0.75% to 3%
E.3 The unit will have a time delay adjusted between 0.3 to 20 Seconds.
E.4 The opsitioner can be field settable for failure of signals in following modes.
Fail to Open
Fail to Close
Fail to Stay put position
F Position Transmitter
F.1 The two wire R/I converter accepts optentiometric input of 100 –235/0-500 Feedback and and converts it to 4-20mA
F.2 External power source from 12-36V DC will have to be connected
F.3 The Positioning accuracy will be less than + 1
F.4 The position transmitter is epoxy filled with IP66 protection
G Signal Isolator
G.1 The isolator an integral part of starter unit, this accepts 4-20mA and gives an Isolated output of 4-20mA
G.2 Zero & Span adjustments are provided for setting
G.2 Load (impedance of the unit will be 500 ohms |